» Division: Unit ventilators and heat recovery

Plate heat recovery exchangers

Application

The plastic heat recovery exchangers are generally used for high-efficiency heat recovery from return air to preheat fresh air supplied to residential, commercial and industrial buildings.

Basic characteristic

Plate heat recovery exchangerThe plate heat exchangers are available in two basic configurations – cross-flow with efficiency approx. 50 to 67 % and counterflow with efficiency 70 to 90 %. All types of the plate exchangers are made of hPS plastic. They are characterized by low weight, high recovery efficiency, hermetic separation of supply and exhaust air, high resistance against aggressive environment (e.g. in swimming pool halls, industrial areas), and low hydraulic pressure drop.

The exchangers are available in number of different designs and sizes according to customers’ needs. For very aggressive environment the are built in a plastic casing. They are available with an optional built-in bypass.

Features

  • High recovery efficiency (54 to 90 % based on type)
  • Designed for airflow 150 m3/h to 17.000 m3/h
  • Low pressure drop
  • Low weight
  • High corrosion resistance in moist and aggressive chemical environment
  • Wide design variability including atypical and special custom-made solutions

Overview of available types

Name Available types Brief description Optional accessories Approx. airflow
[m3/h]
Approx. recovery efficiency
[%]
RVU
  • K/F (basic efficiency)
  • K/G (high efficiency)
  • S1 (counterflow)
  • S2 (counterflow)
  • S3 (counterflow)
General-purpose exchanger in insulated casing, with round and rectangular ports, ceiling-suspended, floor-standing and wall-mounted position
  • bypass (B)
  • mixing damper (C)
  • supply filter (Fe) return filter (Fi)
  • supply damper (Ke)
  • return damper (Ki)
100
to
7.000
50
to
92
RVX
  • K/F (basic efficiency)
  • K/G (high efficiency)
  • S (counterflow)
General-purpose exchangers for higher airflow, for various use due to optional accessories (they basically are “units without fans“)
  • by-pass (B)
  • mixing damper (C)
  • water heating coil (T)
  • water cooling coil (CHW)
  • DX cooling coil (CHF)
  • supply filter (Fe) return filter (Fi)
  • supply damper (Ke)
  • return damper (Ki)
1.000
to
30.000
48
to
85
RV
  • K/F (basic efficiency)
  • K/G (high efficiency)
  • S (counterflow)
General-purpose exchanger for ducted unit design
  • bypass (BP)
200
to
6.000
48
to
85
RVT
  • K/F (basic efficiency)
  • K/G (high efficiency)
Framed design connectable to ductwork air distribution
  • bypass (BP)
1.000
to
24.000
48
to
70
RVT-P
  • K/F (basic efficiency)
  • K/G (high efficiency)
Framed design made of polypropylene connectable to ductwork air distribution – increased chemical resistance - 1.000
to
24.000
48
to
70
RVZ-P
  • K/F (basic efficiency)
  • K/G (high efficiency)
  • S (counterflow)
All-plastic design with increased chemical resistance - 500
to
8.000
48
to
85

RVU RVU
  • General-purpose design in insulated casing, with front access door
  • Built-in cross-flow (K) or counterflow heat recovery exchanger in three sizes (S1, S2, S3), with efficiency up to 90 %
  • Optional built-in bypass (B), mixing damper (C), supply air (Fe) and return air (Fi) filter, supply air (Ke) and return air (Ki) shutoff damper – in any combination
RVX RVX
  • The most general-purpose design; it basically is a „unit without fans“
  • Built-in cross-flow (K) or counterflow (S) heat recovery exchanger
  • Optional built-in bypass (B), mixing damper (C), supply air (Fe) and return air (Fi) filter, water heating coil (T), water cooling coil (CHW), DX cooling coil (CHF), supply air (Ke) and return air (Ki) shutoff damper – in any combination
RV RV
  • General-purpose type with flat flanges
  • Built-in cross-flow (K) or counterflow (S) heat recovery exchanger
  • Generally used together with standard duct elements of most European manufacturers, with unified sizes and connections
  • Optional built-in bypass (B), possibly with an actuator
RVT RVT
  • Cross-flow type (K) built in a frame to be connected to ductwork
  • Unified module with flange width of 710 mm
  • Height of 500, 1000, 1500 and 2000 mm (atypical sizes on request)
  • Optional built-in bypass BP), possibly with an actuator
RVT-P RVT-P
  • Special type with increased chemical resistance; modification of the RVT design
  • Cross-flow exchanger (K) built in a polypropylene frame with flangeless ports and threaded M8 holes for connection to ductwork
  • Unified module with flange width of 710 mm
  • Height of 500, 1000, 1500 and 2000 mm (atypical sizes on request)
RVZ-P RVZ-P
  • Special type with increased chemical resistance
  • Cross-flow exchanger (K) built in a polypropylene frame with flangeless rectangular ports
  • Unified module with flange width of 710 mm
  • Height of 310, 380, 530 and 780 mm (atypical sizes on request)

NEWS
On 24. 4. 2012 new version 6.10. of the selection software for DUPLEX units was released.
On 1. 7. 2011 new version 5.90. of the selection software for DUPLEX units was released.
The current multi-purpose compact DUPLEX units are popular also due to the wide range of versions available, thus allowing the installation of these units not only in a horizontal position, but also vertical, ceiling-suspended or floor-standing (flat) position.
New range of electric air heaters with capacity of 0,9 up to 54,0 kW, round and rectangular types, built-in power elements.
From August 1, 2008 ATREA introduces into its product range three new heat recovery units under the brand name DUPLEX-S 525, 900, 1400.
In October 2006, product range of the unique DUPLEX-S units was extended with a rooftop version in flat position.
DOWNLOAD
 Preliminary (114 kB)
 RVU (323 kB)
 RVX (277 kB)
 RV (153 kB)
 RVT (118 kB)
 RVT-P (65 kB)
 RVZ-P (67 kB)

CONTACT
phone: (+420) 483 368 111
fax: (+420) 483 368 112

[ top ]